EPHS104/156L

Hybrid ESS Liquid-Cooled Cabinet 50 kW / 104 kWh | 50 kW / 156 kWh

Category:

Energy Storage System


Product Features

200%

PV Oversizing

314Ah

Battery Cells

Up to 10 Units in On/Off

-Grid Parallel Operation

Max. 20A PV Input

Current per String

<65dB, Suitable for

Diverse Environments

<10ms EPS

Switching Time

100% Unbalanced

Loads Supported

UL9540A Certified

for Enhanced Safety


Application Scenarios

EPHS104
EPHS104
EPHS104
EPHS104

Product Specifications

Model

EPHS104L

EPHS156L

PV Input

Max. PV Input Power

100 kW

Max. Input Voltage

1,000 V

Rated Operating Voltage

600 V

Start-Up Voltage

180 V

MPPT Voltage Range

150 – 850 V

Max. Input Current

4 × 40 A

Max. Short-Circuit Current

4 × 60 A

No. of MPPTs / Max. Input Strings

4/8

Battery Parameters

Cell Specification

314 Ah

Pack Configuration

1P52S

Rated Current

160 A

Battery Pack Weight / Quantity

350 kg/unit, total 2 units

350 kg/unit, total 3 units

System Capacity

104 kWh

156 kWh

AC Input / Output (Grid)

Rated Output Power

50 kW

Max. Apparent Output Power

50 kVA

Rated Grid Voltage

3/N/PE 220/380 V · 230/400 V

Grid Voltage Range

304 – 460 V

Rated Grid Frequency

50/60 Hz

AC Grid Frequency Range

45 – 55 / 55 – 65 Hz

Rated Grid Output Current

76.0/72.2 A

Max. Output Current

76.0/72.2 A

Max. AC Input Current

152/144.4 A

Power Factor

> 0.99 (0.8 leading … 0.8 lagging)

THD

< 3 %

AC Output (Back-up)

Rated Output Power

50 kW

Max. Apparent Output Power

1.6 times of rated power, 2 s

Back-up Switch Time

< 10 ms

Rated Output Voltage

3/N/PE 220/380 V · 230/400 V

Rated Frequency

50/60 Hz

Rated Output Current

76.0/72.2 A

Max. Imbalance Power Per Phase

33 % rated power

THDv (@ Linear Load)

< 2 %

AC Input (Generator)

Max. Input Power

50 kW

Rated Input Current

76.0/72.2 A

Rated Input Voltage

3/N/PE 220/380 V · 230/400 V

Rated Input Frequency

50/60 Hz

General Data

Dimensions (WxDxH)

1,305 × 1,766 × 1,388 mm

Weight

~1,500kg (With Inverter)

~1,850kg (with inverter)

Protection Level

Battery Cabinet IP55 · Inverter IP66

Operating Temperature Range

−25 °C – 55 °C

Cooling Method

Liquid-cooling

Fire Suppression System

Smoke detector, Heat detector, Alarm sounder,

Aerosol, Sprinkler (Optional: Gas detector + exhaust, Vent plate)

Communication

LAN/RS485

Altitude

≤ 2,000 m

Standards

IEC 62109, IEC 61000, IEC 62619,IEC 63056, IEC 62040,IEC 62477,IEC 62933, UN,38.3, UL9540A, EN 50549-1/-10, G99, VDE-AR-N 4105, CEI 0-21